Replacement of kitchen GFCI that is cracked and caused a wire to pop out, replacement of two switches improperly wired to control a light and a switch controlled receptacle, and replacement of the switch controlled receptacle. Replacement of six single pole 20 amp breakers with 3 double-pole,20 amp breakers to correct shared neutral, multiwire branch circuits. Installation of whole home surge protection with a lifetime warranty and 120kVa of protection. Returned today to complete annual maintenance inspection. While performing our inspection, customer brought to our attention that kitchen and bedroom receptacles were not working throughout the home. We determined the kitchen receptacles were not working due to a bad GFCI that needed to be replaced. The bedroom receptacles were switch controlled, with one being improperly wired. We replaced the kitchen GFCI as well as two switches that were improperly wired and the switch controlled receptacle controlled by the switches. We also no