403 Headquarters Dr. Unit 5
Millersville, MD 21108
(443) 396-3797

Job Locations
for severna park, md


Map of Severna Park MD
Nicholas T.

Nicholas T.


Job Checkin

Install new 12 gauge wire from garage to post light inside PVC. The reason for today’s visit was to assess the garage lights and post light still tripping the breaker. After assessing the issue, we were able to determine that the line going from the garage out to the post is causing the breaker to trip due to bleeding voltage underground. In order to remedy this issue we will be directional boarding a new PVC line from the garage sidewall over to the post location and installing a new line inside. 12/3 Returned today and completed the new line to the post light. We installed PVC from the existing LB on the side of the garage through the ground over to the existing post light. We installed a new 12 two UF underground feeder cable straight from the panel into the existing light and wired. Once completed, we turned everything on and it is working as it should. Nick 410.301.5485

Install new 12 gauge wire from garage to post light inside PVC.
The reason for today’s visit was to assess the garage lights and post light still tripping the breaker. After assessing the issue, we were able to determine that the line going from the garage out to the post is causing the breaker to trip due to bleeding voltage underground. In order to remedy this issue we will be directional boarding a new PVC line from the garage sidewall over to the post location and installing a new line inside.
12/3

Returned today and completed the new line to the post light. We installed PVC from the existing LB on the side of the garage through the ground over to the existing post light. We installed a new 12 two UF underground feeder cable straight from the panel into the existing light and wired. Once completed, we turned everything on and it is working as it should. 

Nick 410.301.5485 Install new 12 gauge wire from garage to post light inside PVC.
The reason for today’s visit was to assess the garage lights and post light still tripping the breaker. After assessing the issue, we were able to determine that the line going from the garage out to the post is causing the breaker to trip due to bleeding voltage underground. In order to remedy this issue we will be directional boarding a new PVC line from the garage sidewall over to the post location and installing a new line inside.
12/3

Returned today and completed the new line to the post light. We installed PVC from the existing LB on the side of the garage through the ground over to the existing post light. We installed a new 12 two UF underground feeder cable straight from the panel into the existing light and wired. Once completed, we turned everything on and it is working as it should. 

Nick 410.301.5485