COD $883.92 Scheduled with Lupo 551-697-5094 The following discrepancies were found during your Semi Annual Fire Inspection that needs to be corrected for Compliance: Improper nozzle placement in plenum. Need to move 1 nozzle to end of hood. Need to remove pyro chem hangers from link housings and replace with s hooks and crimps. Need to add micro switch to control head to connect to building alarm. Alarm company needs to add audible- visual device to kitchen. (Confires will supply Horn strobe) Range nozzles obstructed by shelves. (Customer to remove shelves)