The following discrepancies were found during your Semi Annual Fire Inspection that needs to be corrected for Compliance: JERSEY DEVIL BBQ 113 HOOD #3: Need to redo the piping on this system. It has quarter inch piping that is not allowed per code. Will need to redo with 3/8 pipe. Two Fryers is not covered and will need to add additional coverage. Also, quarter inch piping above all fryers need to redo. (Replace with 2-230 Nozzles) The link line has old style links and will need to replace with newer style link. Need four links for the system. You will need 4-230 sizzler links.