Scheduled with Sam 973-627-8400 The following discrepancies were found during your Semi Annual Fire Inspection that needs to be corrected for Compliance: OUT OF SERVICE SYSTEM: Incorrect nozzles over Range due to back shelf. Will need to re-pipe LPR nozzles for correct coverage. Nozzle not centered over fryer. Will need to re-locate nozzles for proper coverage. Lack of detection over Range. Need to install detector over Range. Plenum nozzle needs to be relocated to end of Hood. Will need to re-locate nozzle for proper coverage.