2/2/23MV Emailed customer regarding inspection date 2/3, waiting on confirmation this customer is on hold. he has an past due invoice that is 118 days past due. lr Sprinkler Inspection Annual Fire Sprinkler Inspection (1 Wet System) Deficiency: Corroded sprinkler heads shall be replaced with new. 1- kitchen by MOD office 155 QR 3/4 ELO 1- janitor closet across from MOD office 1/2” 286 SR chrm pend 1- dish wash area 155 QR 3/4” ELO Deficiency: Missing outer esc located kitchen 2- Viking white Deficiency: Fire sprinkler system is due for gauge change. 1- sprinkler gauge Deficiency: Spare head box will need an additional sprinkler head. 1- 155° chrome pendant extended coverage three-quarter inch sprinkler head. Deficiency: There are two dry pendant heads that are not in a cooler. They are just hanging from the ceiling and must be removed and plugged. 2- 1” Plugs Deficiency: Sprinkler system is due for five year internal obstruction investigation of piping. 2- 4” Victaulic Coupli