Initial Services Performed: Semi-Annual Kitchen System Inspection Deficiencies Discovered: The existing Pyro-Chem Kitchen Knight II PCL 460 system cylinder is PAST DUE for the required 12 year hydrostatic testing. This cylinder is Department of Transportation (DOT) specified therefore requires serialization and testing in an approved testing center as per the DOT. The (1) eye burner needs nozzle protection Scope of Work Proposed: Perform a 12 year hydrostatic test and recharge on the existing cylinder in our DOT approved testing center using the proof of pressure testing method and equipment. Add nozzle protection to the (1) eye bburner. Exclusions: Electrical and /or Plumbing work (if required). Permits (if required). Any changes mandated as a result of an Authority Having Jurisdiction (AHJ) review of the proposed scope of work. Fire Suppression Repair Pyro Chem PCL 4.6 Gallon Hood Cabinet: Initial Services Performed: Semi-Annual Kitchen System Inspection Deficiencies Discovered