Portable Extinguishers and Fire Suppression Inspection Annual Fire Extinguisher Inspection Semiannual Kitchen Fire Suppression System Inspection Masterbox Plugout-Devens Fire Box #149 Deficiency: Kettle Fryer System is non compliant due to system cylinders and co2 cartridge are due for hydro test. These are due every 12 years per nfpa. No signs of a regulator test and this is due every 12 years as well. 1 of 3 cylinders is over drawn. Will need to adjust accordingly. Need to update coverages on the appliance line. Both Fryer systems need all cylinders and co2 cartridges hydro tested. Also no signs of regulator tests. These are all due every 12 years per nfpa. 4 of 6 cylinders are over drawn. Will need to adjust accordingly. Also need to update appliance line coverages to both systems.