Kitchen Hood Suppression Systems - NON COMPLIANT Recently one of our licensed technicians was at your location to perform the service on your fire suppression system. During that inspection the following deficiencies were found on order 13745452 All 3 system past due for the 12 yr hydrostatic services on cylinders, cartridges and regulator tests Kettle fryer system Hydrotest service required on all 3 Ansul cylinders Regulator test required Replacement of double tank cartridge required Repipe each cylinder for a 12 flow max Fryer Front System Hydrotest service required on all 3 Ansul cylinders Regulator test required **- Replacement of double tank cartridge required ** Ensure coverage is met from Ansul manual 4-34.3 as well as remove 3 nozzles from the front of one line and 2 from the rear of the other Fryer Rear System Hydrotest service required on all 3 Ansul cylinders Regulator test required Replacement of double tank cartridge required Ensure coverage is me