Portable Extinguishers and Fire Suppression Inspection FIRE EXTINGUISHERS - QTY UNKNOWN FX TO BE DONE WITH KS KITCHEN SYSTEM - ZONE 3 ANSUL 4.5 GALLON, RED BD - FRY HOOD HYDRO: (2) 2008 ANSUL 3.0 GALLON, RED BD - BROILER HOOD HYDRO: 2008 KS TO BE DONE WITH FX & EL Deficiency: Both Systems are non compliant due to system cylinders are the red type. These cylinders need to be swapped out for silver tanks. Red tanks starting to corrode. Also customer has either a roof leak or the hood cleaning company left a lot of water on top of the broiler hood. Water was leaking through the penetration seal for the broiler appliance. This seal will need to be changed when we return with the new cylinders. Cylinders need are 2x 3g and 1x 1.5g ansul