26 Hampshire Drive
Hudson, NH 03051
(800)244-7531

Job Locations
for fitchburg, ma


Map of Fitchburg MA
Nicholas L.

Nicholas L.


Job Checkin

Kitchen Hood Suppression System - NON COMPLIANT Recently one of our licensed technicians was at your location to perform the service on your fire suppression system. During that inspection the following deficiencies were found on order 14196023 Correct system deficiencies Repair of these deficiencies is essential to overall life safety. Please see attached compliance quote. If you have any questions, feel free to call me. Thank you Mike McDonald 603-988-5512 Fire Suppression Repair The nozzles for the appliance protection are all outside the perimeter of the appliances. The fryer nozzles are not in the proper position. The griddle requires a second 11982 nozzle for its protection.the nozzles for the 6 burner (with back shelf)protection are not the proper ones. The nozzle for the griddle protection is not the proper one ( there is an upright broiler on top of the griddle). The nozzle for the upright broiler is not the proper one. All the pipe and conduit outside the hood is painted