Job Checkin

Gas Station Suppression Inspection GAS STATION SYSTEM PRYO CHEM ATTENDANT - 2 HYDRO: (7)NEW2001,(2)2002NEW, (1)02003NEW Please make sure to email a copy of the GSSUP report to the gas station manager on duty & Ken Silvia whom is the Stop & Shop gas stations supervisor. Deficiency for Pyro Chem ATD-80 960lb: Gas station suppression system is non compliant due to both PAC200 are due for hydro. Both are dated 2007 and are due every 12 years