26 Hampshire Drive
Hudson, NH 03051
(800)244-7531

Job Locations
for sturbridge, ma


Map of Sturbridge MA
Nicholas L.

Nicholas L.


Job Checkin

Fire Suppression Inspection KITCHEN SYSTEM - QTY KS ALL INCLUSIVE Deficiency for Pyro Chem PCL-460 2 Kitchen: System is non compliant due to improper coverage of the chargrill and salamander broiler. Nozzles need to be repiped so that they are postioned correctly per manufacturer manual. Also there is lots of grease build up on and in the conduit above the Chargrill I recommend getting this section of conduit replaced. Grease build up inside conduit could stop the system from working properly. Clean out the best I could for the mean time. see pictures