26 Hampshire Drive
Hudson, NH 03051
(800)244-7531

Job Locations
for gorham, me


Map of Gorham ME
Nicholas L.

Nicholas L.


Job Checkin

Gas Station Suppression, Portable Extinguishers, and Emergency / Exit Lights Inspection GAS STATION - QTY 1 IND50 x 8 2013 x 8 GS TO DO FX AT SAME TIME FIRE EXTINGUISHERS - QTY 5 FX TO BE DONE WITH GS EMERGENCY LIGHT SPOT CHECK - QTY 13 REPAIR AS NEEDED EL TO BE DONE WITH GS Deficiency for Kidde/Badger IND-50 400lb: Gas Station System: XV Control head is on the top of the canopy and is not listed for outside use by the MFG. The control head will need to be placed inside a UL listed weather tight enclosure (will require an electrician to remove and reinstall wires in new enclosure). 3 IND-50 cylinders are due for hydrostatic testing. (all above pumps 5/6 & 7/8) Confirmed 3/26/18 NL