26 Hampshire Drive
Hudson, NH 03051
(800)244-7531

Job Locations
for saco, me


Map of Saco ME
Nicholas L.

Nicholas L.


Job Checkin

Gas Station Suppression, Portable Extinguishers, and Emergency / Exit Lights Inspection GAS STATION SYSTEM - QTY 1 IND50 x 4 -2014 GS TO BE DONE WITH FX FIRE EXTINGUISHERS - QTY 3 FX TO BE DONE WITH GS EMERGENCY LIGHT SPOT CHECK - QTY 3 REPAIR AS NEEDED EL TO BE DONE WITH GS Deficiency for Kidde/Badger IND-50 4: Standard canopy, XV control head and all IND50 cylinders are mounted to the pillars, no fire alarm at this location, pumps reset when devices go back into normal state (not with control head). Also control head is not listed for outdoor use. Needs to be moved into a weather tight enclosure. Will need an electrician.