Kitchen Hood Suppression System - NON COMPLIANT Recently one of our licensed technicians was at your location to perform the service on your fire suppression system. During that inspection the following deficiencies were found on order 14794099 Replace wire and pipe for gas valve control. Re-run of this wire and conduit will call for a new corner pulley as well. Manual pull station is mounted too high per code and needs to be lowered between 42-48" Repair of these deficiencies is essential to overall life safety. Please see attached compliance quote. If you have any questions, feel free to call me. Thank you Mike McDonald 603-988-5512 Price does not include any applicable taxes, those will be added at the time of invoicing based on the local tax codes. Fire Suppression Repair wire for gas valves is spliced together, wire also runs thru black iron pipe. tension wire can only run thru conduit. Will need conduit and corner pulley to fix. manual release is mounted too high at 56" nee