Nicholas L.

Nicholas L.


Job Checkin

Kitchen Hood Suppression System - NON COMPLIANT Recently one of our licensed technicians was at your location to perform the service on your fire suppression system. During that inspection the following deficiencies were found on order 14905371 Cook line added new back shelf range. This coverage will require 3 flow points of protection calling for another cylinder. 1.5 gallon cylinder for appliance line (4 flow points) Another cylinder will call for a large activation cartridge. This would need to be replaced at 12 years anyway. Nozzle drops installed over range Current cylinder in place is due for the 12 year service starting 2019. Included below is the 12 year service to avoid a proposal for the next inspection and save on return service labor. 12 year service includes: 1 tested swap cylinder, new agent, regulator test, new hose/grommet kit, old chemical disposal, shop labor, delivery and install Repair of these deficiencies is essential to overall life safety. Please see attached