Gas Station Suppression, Emergency / Exit Lights, and Portable Extinguishers Inspection GAS STATION - IND50BC x 4 - 2012 GS DO FX AT SAME TIME EMERGENCY LIGHT SPOT CHECK - QTY 3 REPAIR AS NEEDED EL TO BE DONE WITH GS FIRE EXTINGUISHERS - QTY 6 FX TO BE DONE WITH GS Inoperable Deficiency for 10lb ABC Back Room: Gas Station System: System is non compliant due to all cylinders being due for service IND50X4 3X2012- 1X2006. Heat detector above pumps 3/4 did not operate the control head durning testing. Detector will need to be replaced. Also the control head is mounted above the canopy and is not inside a weather tight enclosure. This control head is not listed for out door use. Confirmed 12/6/18 NL Gas Station Suppression, Emergency / Exit Lights, and Portable Extinguishers Inspection GAS STATION - IND50BC x 4 - 2012 GS DO FX AT SAME TIME EMERGENCY LIGHT SPOT CHECK - QTY 3 REPAIR AS NEEDED EL TO BE DONE WITH GS FIRE EXTINGUISHERS - QTY 6 FX TO BE DONE WITH GS Inoperable Deficien