26 Hampshire Drive
Hudson, NH 03051
(800)244-7531

Job Locations
for chester, nh


Map of Chester NH
Nicholas L.

Nicholas L.


Job Checkin

Fire Suppression Inspection LOST - KITCHEN SYSTEM - ZONE 5 PCL 350 HYDRO: 2012 KS TO BE DONE WITH FX Deficiency: system is non compliant due to improper coverage of the range. Currently has one NL-R nozzle and one NL-RH2 nozzle protecting it. The NL-R is incorrect per manufacturer specs. This nozzle needs to be changed to NL-F1 in order for the range to be protected properly. Range has a back shelf that needs to be removed.