Job Checkin

Call Martin when you arrive on site 603-851-1290 and he will let you in. Kitchen Hood Suppression System - NON COMPLIANT Recently one of our licensed technicians was at your location to perform the service on your fire suppression system. During that inspection the following deficiencies were found on order 13306919 Nozzle change required Repair of these deficiencies is essential to overall life safety. Please see attached compliance quote. If you have any questions, feel free to call me. Thank you Mike McDonald 603-988-5512 Fire Suppression Repair system is non compliant due to improper coverage of the range. Currently has one NL-R nozzle and one NL-RH2 nozzle protecting it. The NL-R is incorrect per manufacturer specs. This nozzle needs to be changed to NL-F1 in order for the range to be protected properly. Range has a back shelf that needs to be removed. - repair