Kitchen Hood Suppression System - NON COMPLIANT Recently one of our licensed technicians was at your location to perform the service on your fire suppression system. During that inspection the following deficiencies were found on order 13742340 - Range nozzle are above back shelf and do not meet compliance due to spray pattern. Change nozzle to 2L and relocate pipe to front edge above appliance to miss shelf if agent is ever needed. Repair of these deficiencies is essential to overall life safety. Please see attached compliance quote. If you have any questions, feel free to call me. Thank you Mike McDonald 603-988-5512 Fire Suppression Repair rh2 nozzles above range are directly above the back shelf. Re pipe with F1 nozzles along the front edge of the shelf. Nozzles must be 15-30" above the range. Nozzles can be +or- 6" from the front to back center line aimed at center. (See Chris for F1 nozzles.) Deficiency: rh2 nozzles above range are directly above the back shelf. nozzles should b