Kitchen Hood Suppression System - NON COMPLIANT Recently one of our licensed technicians was at your location to perform the service on your fire suppression system. During that inspection the following deficiencies were found on order 13849767 Plenum and duct nozzle need to be re-positioned as they are installed back to back and this is no longer listed as proper protection. Replacement nozzles required due to heavy grease build up. Auto detection system requires replacement due to the amount of grease in the auto detection conduit and fittings CLIENT RESPONSIBILITY - Exhaust system should have grease cleaning due to current condition. Repair of these deficiencies is essential to overall life safety. Please see attached compliance quote. If you have any questions, feel free to call me. Thank you Mike McDonald 603-988-5512 Fire Suppression Repair Extremely heavy grease build up. Plenum and duct nozzles need to be repiped and replaced conduit and detection line should be replaced Bot