Gas Station Suppression Repair Recently one of our licensed technicians was at your location to perform the service on your fire suppression system. During that inspection the following deficiency was found on order 13492824. - Service and swap out ATD-80 cylinder over pump 1-2 that has lost pressure - 8 total cylinders lack proper pipe length from distribution tee - All cylinders require bracing on discharge pipe Gas Station Canopy Suppression System Repair of these deficiencies is essential to overall life safety. Please see the attached compliance quote. If you have any questions, feel free to call me. Thank you Mike McDonald 603-988-5512 Pyro Chem ATD-80 960lb: Gas Station System: One ATD-80 over pump 1/2 has lost pressure and need to be serviced. 2 cylinders over each pump (8 total) lack the proper 20" of pipe from distribution Tee to last 90. All cylinders lack bracing on discharge pipe. - repair