Fire Suppression Inspection KITCHEN SYSTEM - ZONE 2 PYRO CHEM PCL 300 - snack shack HYDRO: 2004 R 102 . G SSBD - hot plates HYDRO: 2012 new RG 6.0 G X2 new style - main kitchen HYDRO: 2005 (2) R 102 4.5 G SSBD (X2) - front line HYDRO: 2012 new (2) Deficiency: (Both RG6G tanks) Main system is non compliant due to system cylinders need hydro testing. Both tanks are dated 2005 And are due for hydro every 12 years per nfpa. system will also need 2 vent plugs.