FIRE EXTINGUISHERS - QTY 3 GAS STATION - QTY 1 Portable Extinguishers and Gas Station Suppression Inspection Deficiency: Gas station is non compliant due to system cylinders need hydro testing. This test must be performed every 12 years per NFPA. There is no fire alarm tied into the system. Pumps do not shut down apon system activation. Will need to add class k fx in kitchen due to auto fry system