I used this company on Saturday and today. Both times the customer service was excellent. Enjoyed working with the technicians.
Rtu 8 Compressor Burn-out Replacement: LPI MEP Proposes to: Remove and discard faulty compressor / reclaim refrigerant in accordance to EPA guideline and regulations Furnish and install compressor Furnish and install contactor Furnish and neutralize acid in system with acid scavengar Install new high acid liquid line dryer Pressure check system with dry nitrogen Evacuate system Charge system with new refrigerant Check and log operations Work to be performed during normal business hours 8:00 am to 5:00 pm Work to be performed is for compressor Install only. If needed, additional repairs will be at service rates. EXCLUSIONS: Unforeseen issues with system due to defective part(s) Further diagnostics beyond said repairs previous service or diagnostics Roof work or repair Controls or building management *Anything not listed in inclusions *Overtime
Condenser Fan Motor RTU 12: LPI MEP Proposes to: Remove and discard faulty condenser fan motor Furnish and install new condenser fan motor Furnish and install new capacitor Check and log operations Work to be performed during normal business hours 8:00am to 5:00pm Work to be performed is for condenser motor Install only. If needed, additional repairs will be at service rates. EXCLUSIONS: Unforeseen issues with system due to defective part(s) Further diagnostics beyond said repairs Anything not listed in inclusions Overtime Does not include original diagnostics or service