Arrived at location on 8/27/21 - Checked the unit and found out that the elements on ohm were OL. I called manufacture and spoke to Mark and he confirmed that the unit parts were out of stock and were not made anymore. The unit is over 16 years old. Customer would like a quote for a new unit.


Mark B.

Mark B. Job Checkin

Arrived at location on 7/14/21 - Checked out unit and found that the start button was working fine on arrival. Per customer the start button would stick in and not come back out. Tried starting and stopping several times and worked every time will obtain start and stop button and return. Returned to location on 7/23/21 - Returned with parts. Removed old stop and start switch and installed new stop and start switch. Checked operation, ok.


Mark B.

Mark B. Job Checkin

Arrived on site on 7/14/21 - Checked out unit and found on arrival that the water symbol was on display and none of the valves were working. Found that the A2 fuse on the board was open. Ohmed out all the solenoids at 4 ohms and nothing to ground. Installed new fuse and ran unit and left cycle for a period of time, there's no problem. Unit ran at 100% steam and couldn’t get anything to fail. Recommend to run it without over night cooking to see if it fails again and what setting it is in. Could be one of the valves shorting out from time to time. Will call John at 8 or 9 to see what he would like to do.


Mark B.

Mark B. Job Checkin

Arrived at location on 7/6/21 to check on walk in cooler. Unit had ice build up on evap. Thawed with hot water and started unit back up. Checked receiver and it is still at 80% checked super heat and it was at 35 degrees. Tried adjusting but unit would not respond. Will need to replace txt. Unit is R 22. Returned to location on 7/9/21 - picked up parts from supply house. Pumped unit down and removed old txv valve and brazed in new one. Suction pressure was higher and temperature dropped.


Mark B.

Mark B. Job Checkin

Arrived at location on 6/17/21 and checked in with MOD. Customer complained unit not holding temp running at 60 degrees. Plugged unit in to outlet. Temp checked cabinet with digital thermometer. After 5 minutes unit pulled down to 38 degrees. Unit working properly at this time and making temp. Checked customer thermometer. Customer thermometer still reads 60 degrees. Recommend customer replace thermometer


Service C.

Service C. Job Checkin

Came in and checked dishwasher ran it no issues removed side cover saw water leaking from back of unit. ran another cycle found vacuum breaker leaking when it goes into rinse cycle. will have part tomorrow morning and will return. 12-22-20 Returned with part. shut off water and dishwasher. removed vacuum breaker from dishwasher and removed pipes from vacuum breaker and installed them on new one. put new vacuum breaker in place and tightened down. ran 3 cycles to check for leaks, all okay.


Service C.

Service C. Job Checkin

Found MAN ice machine and bin unplugged and water leaking from the ice bin, Bin parts were laying on top of the ice machine, and water was laying in the ice machine drain pan. Pulled drain line from drain and blew backwards then let it drain out.. removed ice. machine front cover and removed drain pan, vacuumed all sludge and blew drain out again, then vacuumed water from underneath and from the floor. Reassembled and turned on. Observed bin draining and machine harvest 2 sheets of ice. everything is working good at this time.


Service C.

Service C. Job Checkin

Call Out - Reach-In Cooler Unit was 43° upon arrival. Found suction line at compressor bent and almost closed off. Straightened out line best possible and unit started working. Also found it slightly low on charge. Unit is cooling and going back down to temp. Everything is running fine at this time..


Service C.

Service C. Job Checkin

Found Steamer top incoming water valve (condensate) leaking out of pinholes in plastic. all components under unit wet. found relay burnt cleaned to test but will need replaced. found flame sense going to ground will need new pilot and gasket. order qwp (expedited freight) per Jason. 6-30-20 Replaced valve, relay and pilot. tested, sys ops okay.


Service C.

Service C. Job Checkin

Came in and upon arrival the Steamer unit was running. per customer he said this morning when the standby light came on then the reset the standby went off and came back again. he said it happened just once today and they drained the unit and filled it again and it works just fine. I drained the unit a couple of times and filled it and the unit works just fine, no issues. blew the yellow valve in case there is any residue of scale so it will go through the drain. left the unit running for a while with no problems, probably some was stuck somewhere and got drained. customer will gave us a call if the issue comes back again. asked customer if he wants us to delime the unit and he will call us to gave us his decision.


Service C.

Service C. Job Checkin

Some of the wires in Oven unit are fried: Found no gas to bottom oven. quick disconnect not seated properly, reseated. tested okay. customer is going to repair top oven.


Service C.

Service C. Job Checkin

checked out Combi Oven unit and found that the sc pump was not running in test mode. drained generator and pulled off pump to find that pump was blocked with lime. cleaned out lime and flushed pump. also found that the drain hose from the pump is leaking. customer is going to replace hose. all other operation okay.


Service C.

Service C. Job Checkin

Found contactor on Ice Machine bad, replaced from truck stock and watched unit drop one batch of ice, Unit is working properly at this time, Unit does need cleaned but don't have time today, will have to return to clean


Service C.

Service C. Job Checkin

Everything on Prep Table unit running properly when I arrived, Found unit to be low on refrigerant, dropped what was left and recharged with factory amount of 134A, checked for leaks with leak detector and bubbles but could not find any, Leak maybe in the cold plate which is not repairable, Unit is dropping in temperature and working properly at this time


Service C.

Service C. Job Checkin

found faults on TBC Oven as follows: F6=EC Temp(electrical controls)156; F5=Mag Temp 16; F2=Lo Temp(cook cavity) 2; F1=Main Blower 1. Cleared all. Inspected control compartment and found signs of excessive component heat stress. Controls are very dirty. All fuse holders cracked, good mag amp draw, but blower control and blower need replaced. Also possible other issues. Per Cust(Dee) DNR. Replaced side panel and left breaker off.