Mark B.

Mark B. Job Checkin

Arrived on, 09-8-23 Matt Found evap coil was frozen solid. Open unit up and checked through system. Will need to thaw unit out and return on Monday morning to further diagnose. Job incomplete. Returned on, 09-11-23 Matt Checked operation of unit. Compressor kicks on soon after unit turns on. Checked relay, is good. Contacts inside look beat, would replace. The thermistor p1 is out of range. Need to replace, is causing to freeze up. The set point was at 0 which is the warmest setting. New thermistor set point is 6. Will return with parts and install. Job incomplete. Completed on, Unplugged unit to be able replace defective parts. Removed and replaced both the thermistor, and the valve insert thermistor. Didn’t install the compressor relay due to it being apart of the board. Unit is holding temp and properly working at this time. Job is complete.


Mark B.

Mark B. Job Checkin

Arrived at location on 7/26/21 - Remove existing Victory 2 door refrigerator. Uncrated and unpacked new Atosa refrigerator. Removed existing refrigerator from kitchen. Installed new Atosa refrigerator in to Kitchen. Took photos of installed unit. Plugged refrigerator into outlet and set temperature controller to set point of 34°. Checked operation okay. note: found small dent on left door and scratch on right door after unpacking. Took photos.


Service C.

Service C. Job Checkin

Checked Combi Oven unit found 2 hot leads burnt off element. repaired wires and replaced terminal ends with hi temp fm/spades. tested turned on and let heat. unit drawing 24amps on l1 16.9 on l2 and 18.5 on l3. turned on and unit preheated in good time no errors. came to 400 and cycled. unit is operational job complete.


Service C.

Service C. Job Checkin

Griddle Unit not in use. Removed front panel. Pilot is lit. Turn on gas thermostat. Burner did not light right away. When it did it popped. Can see the flame is wavy where the pilot crossover tube is. Checked gas pressure. 4.3" wc nat. Adjusted to 4 " as per data plate. Removed thermostat. Checked orifice. It is OK. Compared it to the right orifice. It was identical. The right side is OK. Reassembled all. Made a slight adjustment to the thermostat. Also, the air shutter was not open enough. There was some yellow tipping. Opened further. Turn on thermostats. Now the left burner lights right away and the flame is not wavy. The right burner is OK. as well. Back in service.


Service C.

Service C. Job Checkin

Arrived at location for pizza oven not working, tested outlet, outlet is a 208 volt Outlet, checked power coming into the unit, unit contactor is getting about 204 coming in, cooling fan on unit turns on but unit itself does not turn on - conveyor does not turn on, does not heat. I checked, I then called Lincoln, was on hold for about 30 minutes before Joe answered, the problem has got to be in the fuses, the high limit or the fuse holders or a loose connection. I checked for any loose or broken wire connections, wires seem to be solid and on, connections seem to be solid as well, When I first initially came high limit for unit was tripped, I reset the unit, that's when the cooling fan started running so I also checked the fuse holders and got continuity at the fuse holders, when checking fuse holders I noticed that the ice cube relay Sparks inside and also blew out one of the fuses, got no continuity and power switch either so will order fuses, call ice cube relay and a rocker switch,


Service C.

Service C. Job Checkin

checked Middle unit pilot was out, tried to light, wouldn't hold. traced to red wire from hi limit pulled off valve and red lead from Thermopile was loose. couldn't tighten t pile lead tied into red lead from limit and plugged into valve. lit pilot ,held and brought to temp 350. cycled and pilot held. unit operational job complete.


Service C.

Service C. Job Checkin

Found Walk-In Cooler Box temperature 11F sight glass full low side 17psi high side 365psi blew out condenser coil with compressed air loaded with dust from dryer vents. Sight glass emptied out high side dropped to 217psi. Found liquid line serve cap cracked and Schrader leaking. Tightened Schrader and replaced cap with brass. Recharged unit. Temperature dropping at 3F will take some time due to defrosted product. Unit cooling properly.


Service C.

Service C. Job Checkin

Found Reach-In Freezer Unit trips GFCI breaker right away before controller cycles through self test. Checked wiring only frame htr vaporizer and light powered off power switch. Vaporizer and frame heater good door light switch shorted to ground. Disconnected light circuit in control box will order new switch. Started unit. System operating properly otherwise. 9/26/18 Installed new door switch. Also tightened handle. Reattached wires in electrical box. Light now works. Back in service.


Service C.

Service C. Job Checkin

Found- GFCI breaker on Reach-In Freezer tripped. Reset breaker, compressor starts, breaker trips as soon as evap fan starts. Will order new fan motor. 8/8/18 Follow up - Replaced failed evaporator fan motor. Started unit, cooling properly


Service C.

Service C. Job Checkin

7/12/17 Reset limit and lit pilot but it won't hold. Have 400 mV from thermopile. Tested limit and it is open and will not reset. Put in new hi limit and lit pilot- ok. Pilot holds. Run burner to 300 and cycle. Ok. At temp and ok. Pilot ok. Unit back in service. ** No charge travel and miles per Service Manager


Service C.

Service C. Job Checkin

Gas line leaking from braided hose. Picked up replacement and installed.