7843 Conners Road
Winston, GA 30187
770-800-2665

Job Locations
for mableton, ga


Map of Mableton GA
Jordan E.

Jordan E.


Job Checkin

3 system basic inspection. Upstairs furnace is not safe to operate- I have the gas valve off and the furnace service switch off. The flue pipe is not connected to the furnace, possibly from roof work being done. Flue pipe needs to be fixed by a professional and power and then gas restored to the system. Basement air handler/ heat pump system currently does not operate in heat mode. The thermostat is not controlling the heat pump correctly and the air handler does not have heat strips. There is no emergency heat operation either due to no heat strips. Upstairs furnace is over 20 years old dated 2002 , the ac and coil are dated 2014/2015. The blower motor capacitor is reading half of its required rating and the blower is running higher amps because of this. The ac does cycle on but was too cold to be able to check refrigerant charge. The amp draw,capacitor and contractor are with in specifications. Please see furnace inspection report. Main floor furnace has a weak capacitor for t