Air Conditioner Maintenance 2nd visit • Cleaned AC • Vacuumed debris from condenser • Wash condenser coil • Torque Schrader cores • Tightened king valves • Check for refrigerant leaks at service valves • Clean filter grill • Replaced filter 20x24 & 14x24 • Condenser fan motor amps 1.1 and compressor amps 8.6 • Check contactor • Compressor and OD fan cap MFD 45/10 • Blower amps 4.7 • Inspect coil • Static pressure R/A .4" w.c • Static pressure S/A .2" w.c. Recommended flushing water heater every year due to our hard water and prolonging life of equipment!