Upon arrival homeowner informed me that it’s blowing air it’s just not cold I found that the systems TXV was stuck closed due to age of coil and TXV recommended replacing both because TXV because it is not mechanical and ID coil so no issues down the road. Replaced 20x24x1 return air filter and checked static pressure R.4" S.26" w.c. Checked amp draws on compressor 8.9 and Od fan .9. Checked capacitor mfd ratings 45/5. Checked amp draws on blower 5.6 and checked capacitor 15. We are going to be installing new coil Wednesday 7-1-20. Any questions please call Brandon 602-736-3077