140 Icon Ct.
Sparks, NV 89441
(775) 786-4357

Job Locations
for reno, nv


Map of Reno NV
Eric R.

Eric R.


Job Checkin

Air Conditioner Maintenance: Left Side (Main unit) - Cleaned AC - Vacuumed debris from condenser - Wash condenser coil - Torque Schrader cores - Tightened king valves - Check for refrigerant leaks at service valves - Clean filter grill - Replaced filter - Condenser fan motor 1.0amps - Compressor 11.5Amps - Check contactor - Run Cap 45/5MFD - Inspect coil - Static pressure R/A: .53WC - Static pressure S/A: .2WC Average lifespan for an AC is 15-20 years. This current AC is 18 years old which puts it in prime position for major component failure to occur. Suggest preparing to replace AC Current air conditioner uses r22 refrigerant. R22 has been phased out since 2010 and starting January 1, 2020 it will not longer be made nor able to import into the United States High static pressure on return side of ductwork. Suggest upsizing return air to improve airflow, decrease strain on system and improve efficiency Suggest renewing club membership Air Conditioner Maintenance: Right