Air Conditioner Maintenance 1st visit • Cleaned AC • Vacuumed debris from condenser • Wash condenser coil • Torque Schrader cores • Tightened king valves • Check for refrigerant leaks at service valves • Left homeowner 20x30x1 filter • Condenser fan motor amps.8 and compressor amps 7.8 • Check contactor • Blower cap MFD 10 and compressor and OD fan cap mfd 45/5 • Blower amps 8.9 • Inspect coil • Static pressure R/A .25" w.c. • Static pressure S/A .5" w.c. Recommended servicing Furnace in Fall!