Summary: AC MAINTENANCE. 3rd visit of 3 on Service Club Membership. Verify operation, clean return filter grill and change 20x30 filter, check static pressures on ductwork Return-.3inwc supply-.56inwc, check temperature drop across system 71to 50, check outdoor motor running amperages Fan-1.3A Hermetic Compressor-12a, check dual run capacitor Fan-5.5mfd Herm-44.5mfd, check registers in home are open, check disconnect and tighten lugs, check contactor, check and tighten schrader cores and refrigerant service valve caps, remove compressor blanket and inspect compressor, wash out condensing coil and interior of outdoor unit, reinstall compressor cleaned blanket, check fan blades motor and shaft notice slight leaking on fan motor, reinstall all items and verify operation before leaving. Suggestions: A 5–2-1 compressor saver can be added to the system to help extend the life of the AC. 5-2-1 compressor savers help lower damaging initial amp draws during start up of your AC unit. Start up