Ac diagnostic found ac condenser fan motor not turning on due to the capacitor being failed Recommend maintenance plan, capacitor Customer went with recommendation Air Conditioner Maintenance • Cleaned AC • Vacuumed debris from condenser • Wash condenser coil • Torque Schrader cores • Tightened king valves • Check for refrigerant leaks at service valves • Clean filter grill • Replaced filter • Condenser fan motor .4amps • Check contactor • Blower cap 10MFD • Blower 3.4amps • Inspect coil • Static pressure R/A.31inwc • Static pressure S/A.22iinwc Capacitor new 50/5 Compressor 8.3amps Temperature split 25degrees Customer needs to replace filter next time we will provide filters