AC Diagnostic Arrive and homeowner states that the AC unit is not cooling down the home. Notice air still blowing inside but no cooling. Findings: The outdoor dual run capacitor has failed. The units motor will not start without the outdoor capacitor. The unit needs a new capacitor to get back up and running. Install turbo 200 and verify operation. Also inform homeowner of maintenance plan. Running measurements as follows: Outdoor fan motor-.9A Compressor -14.9A** Voltage-243VAC Temperature drop- 85 to 65 New capacitor-50/5mfd Indoor blower motor-5.0A Suggestions: Replacement Dual run capacitor to get unit back up and running.($294) Service club membership 3 years of maintenance-$192 Maintenance on furnace as well-$192.00 IMPORTANT NOTES! The AC is now 16 years old. The R22 refrigerant that it uses has been phased out by the EPA as of 2020. This means we can no longer guarantee or warranty the cooling operation of the Air Conditioner. If interested in a warranty or guarantee o