Upon arrival homeowner informed me that there AC is not keeping up with set temperature on thermostat, found blower running and OD fan but compressor was not. Tested capacitor and found the herm side was completely dead. Replaced failed 60/5 mfd capacitor and also installed 5-2-1 compressor saver to extend life of compressor and save money on energy cost every year. Checked amp draws on compressor 14.3 and OD fan 1.0, checked volts and resistance across contactor and they were within range. Going to follow back up in a few weeks to do complete maintenance on sytem.