Customer said her ac wasn’t working, turned ac on, system fired up, blower motor struggled to start, 20x30x1 air filter dirty, compressor amps 11.6, condenser fan motor amps .84, contactor burnt, torqued schrader cores and king valves, dual run cap 65/7.5mfd rated for 60/7.5mfd, suction pressure 57 psi, liquid pressure 188 psi, sat temp 30*, evap coil clean, static pressure return .36, supply .3, blower amps 7.3, blower cap 8.6mfd rated for 10mfd, replaced burnt contactor with 40a double pull contactor, replaced dual run capacitor with turbo 200 60/7.5mfd, replaced liquid and suction schrader cores, replace blower motor and single run capacitor at furnace, cleaned furnace blower wheel, changed 20x30x1 air filter, washed condenser coil, refrigerant numbers now 63 psi suction, 200 psi liquid, 35* sat temp, temp drop 22*, tested ac and furnace. This ac uses r22 refrigerant which is phased out by the EPA, therefore there is zero warranty on repairs done to ac, ac is working but did tel