140 Icon Ct.
Sparks, NV 89441
(775) 786-4357

Job Locations
for sun valley, nv


Map of Sun Valley NV
Randy M.

Randy M.


Job Checkin

Air Conditioner Maintenance • Cleaned AC • Vacuumed debris from condenser • Wash condenser coil • Torque Schrader cores • Tightened king valves • Check for refrigerant leaks at service valves • Clean filter grill • Replaced filter • Condenser fan motor .8amps • Check contactor • Blower cap 7.0MFD • Blower 5.7amps • Inspect coil • Static pressure R/A.35 • Static pressure S/A.39 Capacitor 34.8/5mfd out of 50/5 Compressor windings Compressor 6.2amps Findings - blower capacitor is low - ac dual run capacitor is low - dirty filter - system is past its life span and R22 which has been fazed out Recommend replacing air conditioner if not then to replace both capacitor and contactor also purchasing a maintenance plan Blower cap 201.00 without maintenance plan 171.00 with maintenance plan Ac dual run capacitor 375.00 without maintenance plan 319.00 with maintenance plan Contactor 201.00 without maintenance plan 171.00 with maintenance plan Filter