Upon arrival find unit buzzing, find capacitor has failed on hermetic and fan sides. Replaced with turbo 200, 35/5, checked fan motor amps and reading 1 amp. Compressor reading 8 amps. Registers are open and have airflow. Registers reading 64 degrees. Home is very hot, told Julie it is going to take quite a long time to cool down the home, homeowner understands why and what to do to try to cool down home as fast as possible. Unit cooling and functional upon departure.