I completed diagnostics and found the filter clean. I also found both 30A fuses in the disconnect blown. I replaced the fuses. The system is cooling now but I advised The client the hotter it gets the more amps the compressor is gonna run at which could make it go out on overload. System ran for 20min with no issues. The system is operational upon departure.