Call vac system has not been operating properly. It is a 2015 train heat pump split system. Only thing I could find wrong with it is the main zone damper is sticking partially closed when it should be open this He’s causing and airflow restriction on the main zone which is what is creating the ice on the coil.Zone damper needs to be replaced it is a 16 inch and it is in line on hard metal.