Have any feedback for us? We'd love to hear it! Call us at (405) 888-5253 and let us know how we are doing.
System low on r22 Has leaking coil Compressor pulling above max amps Contactor is burnt due to compressor pulling high amps Drain was ran uphill causing water to leak into system and house Heat exchanger is really rusty and weak due to being 30yrs old and having water ran across it System needs replaced for the safety of the tenant Also changed filter and fixed drain