Job Checkin

50/5 capacitor reading 48.8/4.78 Fan motor amps 1.7 max per data plate is 1.9 Compressor amps 23.7 max per data plate is 26.3 Condenser is dirty needs washed Filters are really dirty - customer changed filters while I was there and said they would wash condenser System cooling well Compressor and fan motor running high amps, they are 12yrs old and just working really hard I wouldn’t be surprised if one of them went out Out later that day Customer washed condenser and now system is not cooling anymore so they called me back out Condenser fan motor locked up causing compressor to lockout on overload Will return tomorrow to install fan motor 9-11-19 Returned and installed new motor and system is cooling Compressor is pulling really high amps 22.89 and max is 26.3 compressor is on its last leg