Job Locations
for midwest city, ok


Map of Midwest City OK
Jason B.

Jason B.


Job Checkin

AC not cooling. Filter was clogged and dirty that was inside of unit. At time is service, unit was turned on and was cooling. Unit had a 17 degree temperature split. Unit is working and cooling home now. Due to filter being clogged unit likely froze up when running causing it not to cool. Unit does have high pressures on high side. Unit was 305.8 psig with 46 degrees of sub cooling, and 71.9 psig with 31.5 degrees of superheat. Unit is not cooling efficiently and has a restriction in the metering device. Unit needs to be pumped down, a new metering device installed with a filter drier, evacuated, and the system charge adjusted once it is repaired.