No cool. Upon arrival the system was turned on and the condenser was found to have a hard lock out on the defrost board. The board was reset and the system was given a look over. All electrical was found to be in proper condition. The refrigerant charge was correct at 10° sub cool. The system was also tested in heat mode as well as defrost mode and functioned as it should. At this time if there is an underlying issue it can not be replicated. It is recommended to have the AC checked in the spring when the charge can be more appropriately adjusted.