Completed with ac 2 on 2011 comfort maker 3 ton upstairs and 4 ton main downstairs both gas horizontal in attic. Both units cooling at this time of check up. Upstairs compressor amps are high, capacitor has oil stains, no float switch and short on return with pitted contactor, downstairs fan motor showing wear overheating and short on return. Giving customer the option to do all preventative repairs, minimum repairs, 3 ton condenser upgrade or complete. Customer approved to add compressor saver for upstairs.