Complted with ac 1 on a 2014 Lennox gas horizontal in attic 4 ton, unit cooling at this time or check up. Found start up amps from compressor at 270-310 out of 109 and it rattles when it goes off, weak capacitor rated 45/10 reading 38/7, ecm blower motor is shaking andnmskingnnoise with a rusted dran pan.Giving customer the option to do all preventative repairs, minimum repairs or condenser upgrade. Customer wants to wait for now