Disconnect on outdoor unit was missing replaced with new indoor blower motor sucked up the filter and was attached to the coil up flow unit , cause the unit to trip off high head pressure, cold filter was blocking airflow threw the house, also back side of coil is real dirty, homeowner had filters .