Upon arrival outside compressor unit was non functional Conducted hvac system and electrical components check Components in unit tested good No voltage to disconnect Found fuse not prividing 220 volts Reset fuse and unit turned on and started producing cold air Installed hard start kit/ compressor savor kit to help with high amp startup Would like Accurate to come out for Electrical system check and quote for new panel upgrade and possible rewiring Customer became Accurate Advatage Member